← Trons

Meter Camera Digitizer User Manual

A camera that reads a meter, gauge or dial and serves the value as a point. This manual takes you from the kit to readings in Maintenance Station.

1. What's in the kit

ESP32-CAM main board
ESP32-CAM main boardESP32-CAM
ESP32-CAM-MB micro USB connector board
ESP32-CAM-MB micro USB connector boardESP32-CAM-MB
Power supply, 5 V micro USB
Power supply, 5 V micro USB
Camera case
Camera case
Meter housing case
Meter housing case

You also need:

  • A micro USB data cable. A charge-only cable will not work.
  • A laptop with Chrome or Edge.
  • A Maintenance Station account with an active subscription. Tron software is free with it.
  • A 2.4 GHz Wi-Fi network.

Sourced the hardware yourself? Any hardware with these part numbers installs the same way.

2. Assemble it

Meter Camera Digitizer assembled and fitted over a water meter
  1. Put the parts together

    Seat the ESP32-CAM main board on the ESP32-CAM-MB connector board and fit the pair in the camera case. Fit the camera case on the meter housing case, set the housing over the meter's face, and plug the power supply into the micro USB port.

Leave it unmounted until it is installed: it has to reach your laptop first.

3. Install from Maintenance Station

  1. Connect the Tron to your laptop

    Use the micro USB data cable, straight into the Tron.

  2. Open the installer

    Sign in to Maintenance Station in Chrome or Edge and open Settings → Trons. There is nothing to download and no code to write.

  3. Choose the Tron

    Pick Meter Camera Digitizer and follow the installer.

  4. Install

    Maintenance Station writes the firmware and the settings to the Tron. Keep it plugged in until it finishes, then unplug it.

4. Configure it at its local web page

The Meter Reader Camera's local web page: camera view with the reading area, status, photo settings and device details
  1. Power it on the meter

    Fit the camera over the meter and plug in its power supply. It joins your Wi-Fi network and gets an address from DHCP.

  2. Open its web page

    On a computer or phone on the same network, type the camera's IP address into a browser. Its name on the network is tron-pt- followed by its hardware ID and .local; both the name and the address are listed under Device on the page.

  3. Aim the camera

    Under Camera view, click Live View and aim so the whole meter face fills the frame. The green box is the reading area outlined in Maintenance Station: the meter's digits should sit inside it. Click the photo to see it full size.

    If the numbers are not level, use Rotate photo. 180 flips the picture upside down.

  4. Set how photos are taken

    Under Photo settings, set Photo every (1 to 1440 minutes) and the Resolution; 640 × 480 is recommended, and higher is sharper but slower to send.

    Light brightness sets the white LED by the lens: turn it off for a display that lights itself. Light on time before photo (0 to 60 seconds) gives a solar display time to wake. Click Save settings.

  5. Send a test photo

    Click Send Photo to Station, then check Status: Camera should read OK, and Last photo sent should update. The badge at the top right reads Station connected when the camera can reach Maintenance Station.

5. See the readings in Maintenance Station

The camera sends a photo of the meter to Maintenance Station as often as you set. The reading area is outlined in Maintenance Station, which is where the readings are kept. The link at the bottom of the camera's web page opens the meter there.

The camera needs to reach Maintenance Station over your Wi-Fi. Photos it cannot send wait their turn, and Waiting to send on its web page shows how many.

6. Specifications and notes

Sensor
ESP32-CAM camera module
Measures
The reading on a meter face, gauge, LED panel or analog dial
Network
Wi-Fi (2.4 GHz)
Power
5 V micro USB, power supply in the kit
Base device
ESP32-CAM
  • Mount it square to the dial or display, and make sure the face is lit when the photo is taken.

7. Troubleshooting

The installer can't see the Tron
Use Chrome or Edge: other browsers cannot reach a USB device. Then try another cable. Many micro USB cables only charge and carry no data.
A red fault banner shows at the top of the camera's web page
The banner names the fault. For a weak Wi-Fi signal, move the access point closer or add one near the meter: photos are dropped when the camera cannot send them.
The digits are dark, blurred or cut off
Open the camera's web page, click Live View and re-aim it so the digits sit inside the green reading area. Raise Light brightness for an unlit meter, or turn the light off if it glares on the glass.
Something else
Contact us with the Tron's name and what you are seeing.

Meter Camera Digitizer hardware is supplied as a kit of parts for the customer to assemble. It is not intended for use in critical, life-safety, or other high-risk applications.