Tron Edge User Manual
Plug the Tron Edge into your controls network and commission the building: devices, points, history, alarms and fault detection. It arrives assembled, with the software installed.
Looking for the other one? Tron Gateway User Manual →
1. What's in the box

The Tron Edge arrives assembled, with the Tron Edge software already installed. The label carries the two things you need for setup: the unit's name and its setup code.
You also need an Ethernet cable, and a computer on the same network to open the Tron Edge in a browser.
Bought the software only? Skip to Software only.
2. Connect and power up

Fit the antennas
Screw each antenna onto its gold connector, finger-tight, before you power the unit. Do not power a radio with no antenna on it.
Connect Ethernet
The Tron Edge has two Ethernet ports, marked 1Gb ETH and 2.5Gb ETH. Plug one into a switch on your controls network, or on the building network that reaches it. With no network handy, plug a laptop straight into an Ethernet port.
Connect power
The power input is marked 10–28VDC, with a round jack and a two-pin terminal block. Check the polarity marked above the terminal block before wiring it. The Tron Edge starts as soon as it has power, and the first start takes longer than later ones.
3. First-time setup
Open the Tron Edge in a browser
From a computer on the same network, open
https://<name>.local, using the name on the unit's label (for examplehttps://TronGateway-C47F25.local). You can also use its IP address.The browser warns that the connection is not private, because the unit makes its own certificate: accept the warning to continue.
Enter the setup code
On Welcome to your Tron Edge, enter the Setup code printed on the label. It proves you have the unit in hand, so nobody else on the network can claim it first. It works once.
Create the administrator account
Enter your name, your email and a password of at least 12 characters, twice, then click Create administrator. There is no default password. The unit takes your browser's time zone.
Connect to the internet (optional)
The next step can join a Wi-Fi network or set the Ethernet port, for updates, time sync and remote access. Click Continue to the gateway when done, or to skip. The same settings are under Settings → System.
Connecting a laptop directly: plug it into the Tron Edge's Ethernet port and open the same address. The laptop needs no settings. If the name doesn't open, set the laptop to 10.47.0.10 with subnet mask 255.255.255.0 and open https://10.47.0.1.
4. Commission the building
Set up the site
On Home, open the ⋯ menu on the site card and choose Edit site. Set the name, address and time zone before adding devices: the site's time zone is stamped on its points and used by its schedules.
Set the network interfaces
Usually one port connects to the IT network and the other to the controls network. In Settings → System → Network interfaces, click Edit IP settings, choose DHCP or a static address, and click Apply. Then click Keep in the banner within two minutes, or the old settings come back on their own.
Discover BACnet devices
Open BACnet, click BACnet Actions → BACnet Discovery, and click Scan. Leave Broadcast address blank to send Who-Is on every network the device is on, or enter the controls subnet's broadcast address (for example
10.47.0.255).For a device that won't answer Who-Is, use BACnet Actions → Add BACnet Device and enter its IP address and device instance.
Learn points
In the BACnet list, tick the devices and click Learn. Learning reads each device's object list and brings its objects in as points. You can close the dialog with Run in background; the points appear on each device's Points tab when it finishes.
Apply a template
Open a device, click Edit, choose a Template (or Auto to pick one from the device's name, model and vendor) and click Save. The template names and tags the device's points the same way every time.
Check points and history
On Points, look for any point whose status is not ok. Once samples have had time to build up, chart a few on History Trends.
Set schedules, then review alarms and faults
Add occupied hours on Schedules. Give the unit time to collect history, then go through Alarms and Faults. Alarms during start-up are often wiring, addressing or limit problems.
Add a second administrator
Open Settings → Users and add another admin. There is no password recovery on the unit, so a second administrator is your way back in.
Modbus, SNMP and Haystack sources are added on their own pages under Data Connections. The Documentation page inside the Tron Edge has the full guide to every page, including design values, templates and the fault rule library.
5. Send the data somewhere
The Tron Edge works on its own: history, alarms and users are kept on the unit. To also connect it to your Maintenance Station:
Copy your organization name
In Maintenance Station, open Settings → Tron Gateways and copy the organization name shown there.
Start the claim on the device
On the device, open Settings → Data Export → Maintenance Station, enter the organization name, click Start claim, then copy the claim code it shows.
Add it in Maintenance Station
Back in Settings → Tron Gateways, enter a name for the device (whatever you want to call it) and the claim code, then click Add. The code is good for 15 minutes. Once it shows Connected, the device sends its devices, points and history to your Maintenance Station.
Settings → Data Export also sends data to any other MQTT broker. To use the Tron Edge with Claude, open Settings → MCP Server. To open it from outside the building, turn on Settings → Account → Remote access and approve the code it shows at tronbuildings.com/link. All of these are optional, and all connect outbound only.
6. Software only: Docker Compose
Tron Edge runs as a Docker container on your own Linux server or VM. You need Docker Engine with the compose plugin, on the building network. We send the image file, the compose.yaml file and your license file after your order.
Load the image
Copy the image file to the server and run
docker load -i <image file>.tar.gz.Edit compose.yaml
Set
TZto your time zone. SetTRON_SETUP_CODEto a code of your choosing, so nobody else on the network can create the first administrator. SetTRON_HOST_NAMESto the server's address and name as people will type them, for example192.168.1.137,server.local.The container uses the host's network, because BACnet discovery is a broadcast. Ports 443 and 80 and UDP 47808 must be free on the server.
Start it
Run
TRON_VERSION=<version> docker compose up -d, with the version named in the image file.Create the administrator and install the license
Open
https://<server>/, accept the certificate warning, enter your setup code and create the administrator account. Then install the license file in Settings → Account → License.
Everything is kept in the tron-data volume. To update, load the new image file, set TRON_VERSION to it and run docker compose up -d again. Make a backup first (Settings → Backups).
7. Updates, backups and your license
Updates. Each release is one signed update file. In Settings → Updates, upload the file, review the version and notes, then click Install. The unit keeps the previous version and goes back to it by itself if the new one fails to start.
Backups. Make one in Settings → Backups once the building is commissioned, and before each update.
History. Trend history, alarms and users are stored on the unit and survive restarts and power loss. Deleting a point, device or site deletes its history too.
License. The software license is $1,500 a year and renews until you cancel. A configured unit keeps working indefinitely after a license expires, but loses the ability to change features, devices or points.
8. Troubleshooting
- Nothing happens when I plug it in
- Check the supply is between 10 and 28 V DC and reaches the unit. On the terminal block, check the polarity against the marks above it. The display by the antenna connectors lights once the unit is running.
- The address won't open
- Give a new unit a few minutes: the first start is the slow one. Type the address with
https://in front, and check the name against the label. Check your computer is on the same network. Failing that, plug a laptop straight into the Ethernet port, set the laptop to10.47.0.10/255.255.255.0and openhttps://10.47.0.1. - The setup code is refused
- Enter it exactly as printed on this unit's label: each unit has its own. After several wrong tries the unit makes you wait before trying again.
- A network change undid itself
- Network changes need Keep clicked within two minutes. If your browser was connected through the port you changed, open the unit at its new address and click Keep from there.
- The browser says the connection is not private
- That is expected. Every device starts with a certificate it made itself, so the browser warns the first time. Accept the warning to continue. To remove it for everyone on site, install a certificate from your IT department in Settings → Certificate.
- I see a sign-in page instead of the welcome page
- Someone has already created the administrator account. Ask them to add you in Settings → Users.
- The only administrator's password is lost
- There is no password recovery on the device: it has to be reset. Contact us for help, and add a second administrator on every device so this can't happen.
- Discovery finds no BACnet devices
- Check that the device is on the same subnet as the controllers, then scan again with the controls subnet's broadcast address (for example
10.47.0.255). If routers block broadcasts, tick This address is a BBMD and enter the BBMD's address. Then check the License line under Settings → IoT engine: without a valid license the engine hears devices but returns none of them. - The IoT engine shows as not connected
- It takes about a minute to connect after the device starts. If it stays disconnected, restart it from Settings → IoT engine.
- An update didn't take
- After an update the device restarts and has five minutes to prove itself. If it fails, it puts the previous version back on its own. Roll back in Settings → Updates undoes the last update by hand.
- The claim code is refused in Maintenance Station
- A code lasts 15 minutes and works once. Check the organization name on the device matches the one in Maintenance Station exactly, then click Start claim again for a fresh code. The device needs an outbound internet connection to complete the claim.
Still stuck? Contact us with the name on the unit's label and what you see on screen.
9. Specifications
- Compute
- Raspberry Pi Compute Module
- Memory / storage
- 4GB RAM · 32GB eMMC
- Networking
- 1Gb Ethernet · 2.5Gb Ethernet · Wi-Fi
- LoRaWAN
- 8-channel gateway · US915 / AS923 / AU915 / KR920
- Ports
- HDMI · 2× USB 3.0 · USB 2.0 · USB-C · SD card slot
- Power
- 10–28 V DC, round jack or terminal block
- Protocols
- LoRaWAN · BACnet/IP · Modbus · SNMP · MQTT · OPC-UA · Haystack · SQL · Obix
- Interfaces out
- Web server with Haystack API · MQTT publish · CSV export
- Also runs on
- Docker on your own server
- Price
- $1,500 / year software license · $615 Tron Edge device, once
Tron Edge hardware is supplied as a kit of parts for the customer to assemble. It is not intended for use in critical, life-safety, or other high-risk applications.